All CountriesChange

103 Loop Hanger with Insulation Shield

1030400EG

Features

  • Recommended for the suspension of stationary insulated piping
  • Protection shield is welded to loop before plating

Product Specifications

Part Number 1030400EG
Material Steel
Finish Pregalvanized, Electrogalvanized
Shield Size 4"
Outer Diameter (OD) 4 1/2"
Rod Size (RS) 5/8"
Length (L) 6"
A 7 3/4"
B 3 7/8"
C 1 15/16"
Static Load (F) 1,100 lb
Standard Packaging Quantity 20 pc
UPC 78285636117
UNSPSC 40141725
Insulation Shield Sizing Chart for Iron Pipe
Nominal Iron Pipe Size Insulation Thickness
1/2" 3/4" 1" 1 1/2" 2" 2 1/2"
1/2" 2" 2" 2 1/2" 3 1/2" 5" 6"
3/4" 2" 2 1/2" 2 1/2" 3 1/2" 5" 6"
1" 2" 2 1/2" 3" 4" 5" 6"
1 1/4" 2 1/2" 3" 3" 5" 5" 6"
1 1/2" 2 1/2" 3" 3 1/2" 5" 6" -
2" 3" 3 1/2" 4" 5" 6" -
2 1/2" 3 1/2" 4" 5" 6" - -
3" 4" 5" 5" - - -
3 1/2" 5" 5" 6" - - -
4" 5" 6" 6" - - -
5" 6" - - - - -
Insulation Shield Sizing Chart for Copper Tubing
Nominal Copper Tube Size Insulation Thickness
1/2" 3/4" 1" 1 1/2"
1/2" 1 1/2" 1 1/2" 2 1/2" 3 1/2"
3/4" 2" 2" 2 1/2" 3 1/2"
7/8" 2" 2 1/2" 3" 3 1/2"
1" 2" 2 1/2" 3" 3 1/2"
1 1/4" 2" 2 1/2" 3" 4"
1 1/2" 2 1/2" 3" 3 1/2" 5"
2" 3" 3 1/2" 4" 5"
2 1/2" 3 1/2" 4" 4" 5"
3" 4" 5" 5" 6"
3 1/2" 5" 5" 6" 6"
4" 5" 5" - -
5" 6" 6" - -

Flared edges on sizes through 4” only.

For sizes larger than 6” see Model 403 Clevis Hanger.

Due to a policy of continued product development, specifications are subject to change without notice.