All CountriesChange

Universal Transient Barrier Single Pair: UTB60SPG

CRITEC® Universal Transient Barrier

Print this page

Ordering Information

Region Part / Article #
North America UTB60SPG
Latin America UTB60SPG
Europe/Middle East/Africa 702877
Asia/Australia UTB60SPG

Application Information

  • The UTB series is designed to provide transient protection for equipment from surges induced onto balanced pair signal lines. They are well suited to the protection of industrial equipment such as PLCs and SCADA systems. Other uses include the protection of fire and security alarms, industrial monitoring and control equipment.
  • The UTB-SP (single pair) employs a hybrid multistage clamping circuit, to help ensure the best possible protection to sensitive electronic equipment while maintaining a minimum of line interference and insertion loss.
  • The UTB-SPG (single pair - isolated ground) provides isolation between the shield/common return and protective ground at the point of connection.

Features

  • General purpose barrier – protection of low-voltage circuits and transducers
  • Separate plug and base design – hot swappable feature allows ease of module replacement
  • Multi stage protection – fine over-voltage protection, helps ensure lowest residual surge voltages reach sensitive equipment
  • Common-mode and differential-mode protection – protects against both possible surge conditions
  • Ease of grounding – through DIN mounting rail or via terminal
  • Surge rating to 20 kA 8/20 µs – ideal for exposed wiring
  • Allows for protection of 25 analog signals or 50 digital signals per linear foot of DIN rail space

Product Specifications

Approvals UL® 497B
CE
Connection 1 mm² to 2.5 mm² (#18AWG to 14AWG)
Grounding via terminal or DIN rail connection
Depth 72.00 mm
Enclosure DIN 43 880, UL94V-0 thermoplastic, IP 20 (NEMA-1)
Frequency 3 MHz
Height 90.00 mm
Humidity 0 % RH [Min]
90 % RH [Max]
Loop Resistance 1.0 Ω
Max Continuous Operating Voltage Uc - AC 45 V
Max Continuous Operating Voltage Uc - DC 64 V
Max Discharge Current 20 kA 8/20 µs (L+L)-PE
Max Line Current, IL 2.0 A [Max]
Mounting 35 mm top hat DIN rail
Nominal Voltage - AC 21 V [Min]
42 V [Max]
Nominal Voltage - DC 30 V [Min]
60 V [Max]
Product Series CRITEC® Universal Transient Barrier
Protection Modes Differential & Common Mode
Replacement Module UTB60SPGM
Replacement Module (Europe) 702883
Surge Rated to Meet ANSI®/IEEE® C62.41.2 Cat A, Cat B, Cat C
Technology GDT
MOV
Silicon
Temperature -20°C [Min]
65°C [Max]
Voltage Protection Level (8/20µs) 85 V @ 3 kA
L-L
Weight 0.07 kg
Width 12.00 mm

Application Photos

Click each thumbnail below for a larger version.

Due to a policy of continued product development, specifications are subject to change without notice.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.