United StatesChange
ERICO

Surge Diverter, 20 kA Single Mode DC

Features

  • General purpose barrier protection of 12 or 24 VDC systems and equipment
  • Large surge rating to 20 kA 8/20μs suitable for exposed DC wiring
  • Two stage protection suitable for the protection of power supply feeds
  • High series current rating of 10 A

Specifications

Part Number DSD1201S12 DSD1201S24
Nominal System Voltage (Un) 12 VDC 24 VDC
Max Continuous Operating Voltage (Uc) 15 VDC 28 VDC
Nominal Discharge Current (In) 10 kA 8/20 μs
Max Discharge Current (Imax) 20 kA 8/20 μs
Voltage Protection Level (Up), L-L 30 V @ 3 kA 40 V @ 3 kA
Rated Load Current (IL) 10 A
Protection Modes Common
Differential
Technology Gas Discharge Tube (GDT)
Silicon Avalanche Diode (SAD)
Connection, Solid #10 Max
Connection, Stranded #10 Max
Loop Resistance 0.5 Ω
Mounting 35 mm top hat DIN rail
Enclosure Material UL® 94V-0 thermoplastic
Enclosure Rating IP 20
NEMA®-1
Remote Contacts No
Terminal Torque 22 in lb Max
Temperature -40 to 176 °F
Module Width 1 M
Depth (D) 2.68"
Height (H) 3.54"
Width (W) 0.69"
Unit Weight 0.3 lb
Complies With ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C
Replacement Module DSD1201S12M DSD1201S24M

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ANSI is a registered trademark of American National Standards Institute.
IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
NEMA is a registered service mark of National Electrical Manufacturers Association.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Video

Brochures

Catalogs

Technical

Warranties