United StatesChange
ERICO

High Speed Data Line Protector

Features

  • Multi-stage protection with primary or combination primary/secondary protectors
  • 10 pair protector
  • Provides both L-L and L-PE protection modes for comprehensive protection
  • Simple installation into Krone® LSA disconnect block
  • Data Line Terminator (DLT) available where screw terminal connections are required

Specifications

Part Number HSP10K12 HSP10K36 HSP10K72 HSP10K230
Max Continuous Operating Voltage (Uc) 13 VDC 40 VDC 65 VDC 190 VDC
Max Discharge Current (Imax), L+L-PE 20 kA 8/20 μs
Rated Load Current (IL) 150 mA
Frequency 12 MHz Max
Transmission Rate 8 Mb/s
Protection Modes L-L
L-PE
Technology Multi-stage
Connection Type Krone® LSA-PLUS
Impedance Balance 55 dB Max
Insertion Loss .4 Db Max
Return Loss 20 dB Max
Loop Resistance 16.4 Ω 6.6 Ω
Temperature -4 to 140 °F
Enclosure Material UL® 94V-0 thermoplastic
Depth (D) 0.83"
Height (H) 1.36"
Width (W) 4.92"
Unit Weight 0.05 lb
Certification Details UL® 497
Certifications CE
C-Tick
cULus
A-Tick
CE
C-Tick
cULus

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

Krone is a registered trademark of ADC GMBH.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Video

Brochures

Catalogs

Certifications

cUL QVGV7.E321473
CAN/CSA C22.2 No. 226
UL QVGV.E321473
ANSI/UL 497

Datasheets

ERITECH SLP/HSP & SLP
299 KB English

Technical

Warranties