United StatesChange
ERICO

Rail Transient Barrier Replacement Module

Specifications

Part Number RTB12S3M RTB30S3M RTB50S2M RTB60S1M
Nominal System Voltage (Un) 12 VDC
9 VAC
30 VDC
21 VAC
50 VDC
35 VAC
60 VDC
43 VAC
Max Continuous Operating Voltage (Uc) 18 VDC
12 VAC
33 VDC
23 VAC
65 VDC
50 VAC
85 VDC
60 VAC
Max Discharge Current (Imax) 20 kA 8/20 μs
Rated Load Current (IL) 1.5 A 3.0 A 10.0 A
Voltage Protection Rating (VPR) 15.0 V @ 3 kA 40.0 V @ 3 kA L-L 200.0 V @ 3 kA 240.0 V @ 3 kA
Inductance 188 µH 40 µH
Loop Resistance 0.8 Ω 0.4 Ω 0.1 Ω
Enclosure Material UL® 94V-0 thermoplastic
Temperature -40 to 176 °F
Depth (D) 1.92"
Height (H) 1.78"
Width (W) 0.71"
Unit Weight 0.15 lb

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Video

Brochures

Datasheets

Technical

Warranties