United StatesChange
ERICO

Spark Gap Diverter Replacement Module

Specifications

Part Number SGD125M
Measured Limiting Voltage (MLV) 2,420 VAC
Voltage Protection Level (Up) 1,600 V @ 20 kA
Max Discharge Current (Imax), Per Mode 60 kA 8/20 μs
Impulse Current (Iimp) 25 kA 10/350 μs
Follow Current Extinguishing Capability 100 A @ 0.5 MA
Max Operating Current 0.5 mA
Frequency 50 – 60 Hz
Short Circuit Current Rating (SCCR) 25 kA
Enclosure Material UL® 94V-0 thermoplastic
Temperature -40 to 176 °F
Module Width 1 M
Depth (D) 1.92"
Height (H) 1.78"
Width (W) 0.69"
Unit Weight 0.05 lb

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Brochures

TDXs
823 KB English

Catalogs

Certifications

cUR VZCA8.E325047
CSA C22.2 No. 8, CSA Electrical Notice No. 516
UR VZCA2.E325047
ANSI/UL 1449

Datasheets

TDXM Modular Series
86 KB English

Technical

Warranties