United StatesChange
ERICO

Replacement Module for UTB, Dual Pair Single Power

Features

  • Multi-stage protection and fine over-voltage protection helps ensure lowest residual surge voltages reach sensitive equipment
  • Common-mode and differential-mode protection protects against both possible surge conditions
  • Designed for compact protection of signal and power supply in one compact housing

Specifications

Part Number UTB30DPSM
Nominal System Voltage (Un) 24 - 48 VAC
12 - 60 VDC
Max Continuous Operating Voltage (Uc) 48 VAC
60 VDC
Rated Load Current (IL) 5 A
Frequency 0 – 60 Hz
Loop Resistance 0 Ω
Max Discharge Current (Imax), Per Mode 15 kA 8/20 μs
Protection Modes Common
Differential
Technology Gas Discharge Tube (GDT)
Metal Oxide Varistor (MOV)
Silicon Avalanche Diode (SAD)
Voltage Protection Level (Up), L-L 220 V @ 3 kA
Temperature -4 to 149 °F
Enclosure Material UL® 94V-0 thermoplastic
Depth (D) 1.7"
Height (H) 2.57"
Width (W) 0.47"
Unit Weight 0.05 lb
Complies With ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ANSI is a registered trademark of American National Standards Institute.
IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Brochures

Catalogs

Technical

Warranties