United StatesChange
ERIFLEX

TDL Compact Four Pole Distribution Block, 400 A

Features

  • Connect ERIFLEX FLEXIBAR, insulated braided conductor or cable with lug on line side
  • Tinned copper bars allows for copper or aluminum cable
  • Transparent protection covers
  • Easy and safe connections
  • Easily clips onto DIN rail or mounts to panel with screws
  • Solid bars provide reliability
  • Input separated from outputs
  • Supports wiring from both sides
  • Design allows for visual inspection of conductor and confirmation of connection
  • Large end terminals
  • High percentange of fill ratio
  • Wiring with or without terminal
  • Halogen free
  • RoHS compliant

Specifications

Material: Copper; Thermoplastic
Finish: Tinned
Part Number TDL-400A
Article Number 563995
Max Current Rating, IEC 400 A
Max Current Rating, UL/CSA 400 A
Short Term Withstand Current (Icw) 1s 23 kA
Peak Short Circuit Current (Ipk) 51 kA
Max Working Voltage, IEC (Ui) 1,000 VAC
1,500 VDC
Max Working Voltage, UL (Vin) 600 V
Line Side Number of Connections 1
Line Side Compact Stranded Wire Size 35 - 120 mm²
Line Side Conductor Width 20 – 24 mm
Line Side Stranded Wire Size - Ferrule 35 – 120 mm²
Line Side Wire Size 1/0 – 250 kcmil
Load Side Number of Connections 14
Load Side Compact Stranded Wire Size (1) 10 - 50 mm²
(2) 10 - 35 mm²
(4) 6 - 25 mm²
(7) 2,5 - 16 mm²
Load Side Stranded Wire Size - Ferrule (1) 10 - 35 mm²
(2) 10 – 25 mm²
(4) 6 - 16 mm²
(7) 2,5 - 10 mm²
Load Side Wire Size (1) #6 – 1/0
(2) #8 - #1
(4) #10 - #3
(7) #10 - #5
Depth (D) 4 3/4"
Height (H) 6.14"
Width (W) 8.82"
Unit Weight 3.73 lb
Enclosure Rating IP 10
Flammability Rating UL® 94V-0
Complies With IEC® 60947-7-1
Design Guideline for Distribution Blocks, Power Blocks and Power Terminals
Derating according to Ambient* Temperature (°F) to maintain working temperature of 185°F
Ambient Temperature (°F) 86° 95° 104° 113° 122° 131° 140° 149° 158° 167°
Derating Coefficient (d) 1 1 1 0.94 0.88 0.82 0.75 0.67 0.58 0.47
*environment around the terminal blocks inside the enclosure
Line side and load side number of connections are per pole.

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

IEC is a registered trademark of the International Electrotechnical Commission.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Applications

Brochures

Catalogs

Certifications

cUR XCFR8.E198301
CSA C22.2 No. 158
UR XCFR2.E198301
ANSI/UL 1059

Datasheets