United StatesChange
ERIFLEX

TR Four Pole Distribution Block, 125 A

Features

  • Easily clips onto DIN rail or mounts to panel with screws
  • Equipped with a current input plug
  • Bolts included for output connections
  • Transparent protection cover
  • Easy accessibility for wiring
  • Ready to use out of the box, saving installation time and labor
  • RoHS compliant

Specifications

Material: Copper; Glass Fibre Reinforced Polyamide; Plexiglass
Part Number TR-125A
Article Number 563150
Max Working Voltage, IEC (Ui) 1,000 V
Peak Short Circuit Current (Ipk) 40 kA
Short Term Withstand Current (Icw) 1s 8.4 kA
Line Side Number of Connections 1
Load Side Number of Connections 5
Thread Size 1 (TS1) M5
Thread Size 2 (TS2) M6
Depth (D) 4.61"
Height (H) 4.96"
Width (W) 5.91"
Unit Weight 1.51 lb
Flammability Rating UL® 94V-0
Complies With IEC® 60439.1
IEC® 61439.1
IEC® 60695-2-12 (Glow Wire Test 960 °C)
Thread Size 2 represents input plug.
Line side and load side number of connections are per pole.

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

IEC is a registered trademark of the International Electrotechnical Commission.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Brochures

Catalogs

Certifications

Datasheets