United StatesChange
ERIFLEX

PPS Presswelded Power Shunt

Features

  • Press welded laminations are welded to each other through direct current applied to pieces under pressure
  • Press welding forms a solid palm with the properties of a plain bar
  • Smaller cross section for same capacity
  • Runs cooler than equal section

Specifications

Material: Copper
Finish: Plain
Lamination Thickness: 0.012"
Part Number Article Number Cross Section(kcmil) ∆T 30 K(A) ∆T 50 K(A) L(") H(") A(") B(") C(") Unit Weight(lb) 2 Bar Current Coefficient
PPS40X5-50-180 566000 394.70 572 758 7.10 1.77 1.97 1.58 0.20 0.860 1.72
PPS40X10-50-220 566020 789.41 849 1,125 8.66 2.28 1.97 1.58 0.39 2.050 1.72
PPS50X10-80-280 566030 986.76 1,022 1,354 11.00 2.28 3.15 1.97 0.39 3.175 1.72
PPS80X10-100 566040 1,578.82 1,511 2,002 12.60 2.05 3.94 3.15 0.39 5.787 1.65
PPS100X10-100 566050 1,973.52 1,825 2,418 11.80 2.13 3.94 3.94 0.39 6.757 1.60
PPS100X10-110 566060 1,973.52 1,825 2,418 14.20 2.09 4.33 3.94 0.39 7.959 1.60
PPS100X15-110 566070 2,960.28 2,178 2,886 14.20 2.24 4.33 3.94 0.59 11.872 1.60
When used in parallel, the two shunts must be spaced with a minimum distance equal to the thickness of the shunt to allow air cooling.

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

Brochures

Catalogs

Flexible Conductors
63.23 MB English

Certifications

Datasheets