United StatesChange
ERICO

Service Entrance Suppressor, 40 kA DC

Features

  • Compact NEMA®-4X enclosure design can be flush mounted or installed in a small space
  • Mounting bracket available for mounting within panel backplane

Specifications

Part Number SES40300DC SES40600DC
Nominal System Voltage (Un) 300 VDC 600 VDC
Distribution System DC 2W+G
Max Continuous Operating Voltage (Uc) 360 VDC 600 VDC
Frequency 0 – 60 Hz
Short Circuit Current Rating (SCCR) 100 kA
Nominal Discharge Current (In) 20 kA 8/20 μs 10 kA 8/20 μs
Max Discharge Current (Imax) 40 kA 8/20 μs
Voltage Protection Rating (VPR) 1,500.0 V @ 3 kA 2,500.0 V @ 3 kA
Status Indication LED
Technology MOV with thermal disconnect
Lead Length 20"
Lead Size #12
Temperature -40 to 176 °F
Enclosure Material UL® 94V-0 thermoplastic
Enclosure Rating NEMA®-4X
Mounting 3/4” straight nipple with conduit nut
Unit Weight 0.4 lb
Certification Details UL® 1449 Edition 3 for DC General Use
UL® 1449 Edition 3 Type 1/2, 20 kA Mode
UL® 1449 Edition 3 for DC PV Use
UL® 1449 Edition 3 Type 1/2, 10 kA Mode
Complies With ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C
Depth (D) 2.52"
Height (H) 2.44"
Width (W) 3.96"

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ANSI is a registered trademark of American National Standards Institute.
IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
NEMA is a registered service mark of National Electrical Manufacturers Association.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Brochures

Catalogs

Certifications

cUL VZCA7.E325047
CSA C22.2 No. 8 + 42 + Elect Not No. 516, CAN/CSA
UL VZCA.E325047
ANSI/UL 1449

Instruction Sheets

Technical

Warranties