United StatesChange
ERICO

Modular TDX Panel Protector, 200 kA with Surge Counter

Features

  • Transient Discriminating (TD) Technology provides increased service life
  • Modular design allows easy replacement of surge modules
  • Built-in features include TD Technology, thermal protection and short circuit current fusing
  • Compact NEMA®-4 enclosure design can be flush mounted or installed in a small space
  • Status indication flag per mode, voltage presence LEDs, audible alarm and voltage-free contacts providing remote status monitoring
  • 200kA 8/20μs maximum surge rating provides protection suitable for service entrance, main-distribution panels and highly exposed applications

Specifications

Part Number TDX200S120208 TDX200S120240 TDX200S277480 TDX200S347600
Nominal System Voltage (Un) 120/208 V 120/240 V 277/480 V 347/600 V
Distribution System 3Ph 4W+G 1Ph 3W+G 3Ph 4W+G
Max Continuous Operating Voltage (Uc) 170/276 VAC 320/550 VAC 550/1100 VAC
Stand-off Voltage 240/415 VAC 240/480 VAC 480/831 VAC 790/1370 VAC
Frequency 50 – 60 Hz
Short Circuit Current Rating (SCCR) 200 kA
Nominal Discharge Current (In) 100 kA 8/20 μs 80 kA 8/20 μs
Max Discharge Current (Imax), Per Phase 200 kA 8/20 μs
Impulse Current (Iimp) 20 kA 10/350 μs
Impulse Current (Iimp), N-PE
Impulse Current (Iimp), Per Mode 20 kA 10/350 μs
Voltage Protection Rating (VPR), L-L
Voltage Protection Rating (VPR), L-N 600 V @ 3 kA
1,200 V @ 20 kA
1,000 V @ 3 kA
1,800 V @ 20 kA
1,800 V @ 3 kA
2,600 V @ 20 kA
Protection Modes L-N
L-PE
N-PE
Status Indication LED
Mechanical flag
Audible alarm
Technology TD technology with thermal disconnect
Over-current replaceable cartridge fusing
Remote Contacts Yes
Lead Length 30"
Lead Size #10
Ground Lead Length 36"
Temperature -40 to 176 °F
Enclosure Material Metal
Enclosure Rating IP 65
NEMA®-4
Mounting 3/4” straight nipple
Surge Counter Yes
Depth (D) 3.07"
Height (H) 9.45"
Width (W) 5.12"
Unit Weight 4.4 lb
Certification Details UL® 1449 Edition 3 Type 2, 20 kA Mode
Complies With ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C
ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs
IEC® 61643-1 Class I, Class II
Replacement Module TDS150M150 TDS150M277 TDS150M560
Service Configuration: Delta
Part Number TDX200S120240D TDX200S240D TDX200S480D
Nominal System Voltage (Un) 120/240 V 240 VAC 480 V
Distribution System 3PhΔ 4W+G 3PhΔ 3W+G
Max Continuous Operating Voltage (Uc) 170/276 VAC 276 VAC 550 VAC
Stand-off Voltage 240/415 VAC 415 VAC 790 VAC
Frequency 50 – 60 Hz
Short Circuit Current Rating (SCCR) 200 kA
Nominal Discharge Current (In) 100 kA 8/20 μs 80 kA 8/20 μs
Max Discharge Current (Imax), Per Phase 200 kA 8/20 μs
Impulse Current (Iimp) 20 kA 10/350 μs
Impulse Current (Iimp), N-PE
Impulse Current (Iimp), Per Mode 20 kA 10/350 μs
Voltage Protection Rating (VPR), L-L 1,000 V @ 3 kA
1,800 V @ 20 kA
1,800 V @ 3 kA
2,600 V @ 20 kA
Voltage Protection Rating (VPR), L-N 600 V @ 3 kA
1,200 V @ 20 kA
Protection Modes L-N
L-PE
N-PE
Status Indication LED
Mechanical flag
Audible alarm
Technology TD technology with thermal disconnect
Over-current replaceable cartridge fusing
Remote Contacts Yes
Lead Length 30"
Lead Size #10
Ground Lead Length 36"
Temperature -40 to 176 °F
Enclosure Material Metal
Enclosure Rating IP 65
NEMA®-4
Mounting 3/4” straight nipple
Surge Counter Yes
Depth (D) 3.07"
Height (H) 9.45"
Width (W) 5.12"
Unit Weight 4.4 lb
Certification Details UL® 1449 Edition 3 Type 2, 20 kA Mode
Complies With ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C
ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs
IEC® 61643-1 Class I, Class II
Replacement Module TDS150M150
TDS150M240
TDS150M240 TDS150M560

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ANSI is a registered trademark of American National Standards Institute.
IEC is a registered trademark of the International Electrotechnical Commission.
IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
NEMA is a registered service mark of National Electrical Manufacturers Association.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Applications

Brochures

Wind Power Solutions
1.95 MB English

Technical

Warranties