United StatesChange
ERICO

Ground Rod Clamp, Rod to Conductor, Bronze

Features

  • For use with copper-bonded ground rods
  • Parts that are UL Listed are suitable for direct burial in earth or concrete

Specifications

Material: Silicon Bronze
Torque: 150 – 300 in lb
Part Number Ground Rod Diameter, Nominal Ground Rod Diameter, ActualØ Conductor Size Wrench Size Certifications
CP38 3/8" 0.38" #10 Solid - #2 Stranded, 6 mm² Solid - 25 mm² Stranded 3/8" cULus
CP58 1/2" – 5/8" 0.50" – 0.56" #10 Solid - #2 Stranded, 6 mm² Solid - 25 mm² Stranded 1/2" CSA, cULus
CP34 1/2" – 3/4" 0.50" – 0.68" #10 Solid - 1/0 Stranded, 6 mm² Solid - 50 mm² Stranded 1/2" CSA, cULus
Torque: 150 – 450 in lb
Part Number Ground Rod Diameter, Nominal Ground Rod Diameter, ActualØ Conductor Size Wrench Size Certifications
HDC12 1/2" 0.50" #10 Solid - #2 Stranded, 6 mm² Solid - 25 mm² Stranded 1/2" CSA, cULus
HDC58R 5/8" 0.56" #8 Solid - 1/0 Stranded, 10 mm² Solid - 50 mm² Stranded 1/2" CSA, cULus
HDC58 5/8" 0.56" #8 Solid - 1/0 Stranded, 10 mm² Solid - 50 mm² Stranded 9/16" CSA, cULus
HDC34 3/4" 0.68" #8 Solid - 1/0 Stranded, 10 mm² Solid - 50 mm² Stranded 9/16" CSA, cULus
HDC34SP 3/4" 0.68" #8 Solid - 3/0 Stranded, 10 mm² Solid - 70 mm² Stranded 9/16" CSA
HDC1 1" 1.00" #8 Solid - 4/0 Stranded, 10 mm² Solid - 95 mm² Stranded 9/16" cULus

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

CSA, CSA-US and C-CSA-US are registered trademarks of Canadian Standards Association.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.