United StatesChange
nVent ERICO

Replacement Module for DSD, 50 kA

Features

  • Replacement module for Surge Diverter, 50 kA DSD DC

Specifications

Part Number DSD50M385DC DSD50M615DC DSD50M745DC DSD50M1060DC
Max Discharge Current (Imax) 50 kA 8/20 μs
Max Continuous Operating Voltage (Uc) 300 VDC 600 VDC 750 VDC 1,000 VDC
Voltage Protection Rating (VPR) 1.8 kV @ 3 kA 2.0 kV @ 3 kA 2.5 kV @ 3 kA
Nominal Discharge Current (In) 20 kA 8/20 μs 10 kA 8/20 μs
Enclosure Material UL® 94V-0 Thermoplastic
Temperature -40 to 176 °F
Module Width 1 M
Depth (D) 1.91"
Height (H) 1.78"
Width (W) 0.71"
Unit Weight 0.15 lb

nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Brochures

Wind Power Solutions
1.94 MB English

Certifications

UR VZCA2.E325047
ANSI/UL 1449

Instruction Sheets

Warranties