Features

  • Uses a hybrid Transient Voltage Surge Suppression (TVSS) filter device that incorporates TD technology
  • Capacitive filtering and voltage dependent metal oxide varistors provide high-energy surge suppression
  • Active parallel filter removes common disturbances in electrical environment
  • Flying lead monitors status of surge suppression components in each phase

Specifications

Part Number EPD120240TDFL
Nominal System Voltage (Un) 120/240 V
Max Continuous Operating Voltage (Uc) 150/300 VAC
Stand-off Voltage 240/480 VAC
Frequency 50 – 60 Hz
Aggregate Surge Rating 206 kA 8/20 μs
Voltage Protection Level (Up) 600 V @ 10 kA L-N
870 V @ 20 kA L-N
450 V @ 3 kA L-N
400 V @ 500 A
Short Circuit Current Rating (SCCR) 200 kA
Filtering -40 dB @ 100 kHz
Lead Length 24"
Lead Size #12
Distribution System 1Ph 3W+G
Protection Modes L-N
L-PE
Status Indication LED
Technology TD technology with EMI/RFI filter
Mounting 1/2” straight nipple
Humidity 0 – 90 % RH
Temperature -40 to 158 °F
Enclosure Material Metal
Enclosure Rating NEMA®-1
Depth (D) 4.3"
Height (H) 6.3"
Width (W) 6.3"
Unit Weight 6 lb
Complies With ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C
ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 2, 50 kA 8/20 μs
AREMA® requirements

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ANSI is a registered trademark of American National Standards Institute.
AREMA is a registered trademark of American Railway Engineering and Maintenance-of-Way Association, Inc.