United StatesChange
nVent ERIFLEX

MBJYG Grounding and Bonding Braid, Tinned Copper, Halogen Free

MBJYG Grounding and Bonding Braids are a reliable and convenient ground solution for applications that require flexibility and durability. Designed with halogen-free and flame retardant yellow green insulation, MBJYG braids are made with tinned copper ground braids and solid palms that are ready to install without any additional cutting, stripping, crimping or punching. MBJYG braids also do not require the addition of tin or crimped lugs and the proprietary manufacturing process helps optimize the electrical contact between each wire and helps eliminate moisture issues in the palms, helping prevent corrosion and extend the useful life of the braid.

Features

  • Complete range of earth/ground flexible connections from 6 - 25 mm² (11.84 - 49.33 kcmil) cross section and from 100 - 300 mm (3.937" - 11.811") length
  • Integral palm, without tin or crimped lugs for superior electrical contact and tensile strength resistance
  • Resistant to vibration and fatigue, reducing maintenance
  • Provides weight savings, material savings and lower impedance when compared to similar lugged cables with insulation
  • Ready to use out of the box, eliminates the need for cutting, stripping, crimping and punching
  • Halogen free and flame retardant yellow green insulation
  • Quick and easy to install
  • Recommended by the EMC/EMI directives and less impedance than cables
  • RoHS compliant

Specifications

Material: Copper; Polyolefin
Finish: Tinned
Dielectric Strength: 15 kV/mm
Flammability Rating: UL® 224 VW-1
Halogen Free Rating: EN 14582
Nominal Voltage, UL/CSA/IEC: 600 V
Working Temperature: -67 to 257 °F
Complies With: IEC® 60439.1; IEC® 61439.1
Part Number Article Number Intensity ThicknessT Cross Section LengthL Hole SizeHS A B Unit Weight
MBJYG6-100-6 563601 40 A 0.043" 11.84 kcmil 3.937" 0.256" 0.433" 0.709" 0.026 lb
MBJYG6-150-6 563602 40 A 0.043" 11.84 kcmil 5.906" 0.256" 0.433" 0.709" 0.037 lb
MBJYG6-200-6 563603 40 A 0.043" 11.84 kcmil 7.874" 0.256" 0.433" 0.709" 0.051 lb
MBJYG6-250-6 563604 40 A 0.043" 11.84 kcmil 9.843" 0.256" 0.433" 0.709" 0.062 lb
MBJYG6-300-6 563605 40 A 0.043" 11.84 kcmil 11.811" 0.256" 0.433" 0.709" 0.073 lb
MBJYG10-100-6 563606 75 A 0.043" 19.74 kcmil 3.937" 0.256" 0.433" 0.709" 0.026 lb
MBJYG10-150-6 563607 75 A 0.043" 19.74 kcmil 5.906" 0.256" 0.433" 0.709" 0.037 lb
MBJYG10-200-6 563608 75 A 0.043" 19.74 kcmil 7.874" 0.256" 0.433" 0.709" 0.051 lb
MBJYG10-250-6 563609 75 A 0.043" 19.74 kcmil 9.843" 0.256" 0.433" 0.709" 0.062 lb
MBJYG10-300-6 563611 75 A 0.043" 19.74 kcmil 11.811" 0.256" 0.433" 0.709" 0.073 lb
MBJYG16-100-8 563612 120 A 0.059" 31.57 kcmil 3.937" 0.335" 0.591" 0.787" 0.044 lb
MBJYG16-150-8 563613 120 A 0.059" 31.57 kcmil 5.906" 0.335" 0.591" 0.787" 0.062 lb
MBJYG16-200-8 563614 120 A 0.059" 31.57 kcmil 7.874" 0.335" 0.591" 0.787" 0.079 lb
MBJYG16-250-8 563615 120 A 0.059" 31.57 kcmil 9.843" 0.335" 0.591" 0.787" 0.097 lb
MBJYG16-300-8 563616 120 A 0.059" 31.57 kcmil 11.811" 0.335" 0.591" 0.787" 0.115 lb
MBJYG25-100-8 563617 150 A 0.059" 49.34 kcmil 3.937" 0.335" 0.866" 1.102" 0.066 lb
MBJYG25-150-8 563618 150 A 0.059" 49.34 kcmil 5.906" 0.335" 0.866" 1.102" 0.097 lb
MBJYG25-200-8 563619 150 A 0.059" 49.34 kcmil 7.874" 0.335" 0.866" 1.102" 0.123 lb
MBJYG25-250-8 563621 150 A 0.059" 49.34 kcmil 9.843" 0.335" 0.866" 1.102" 0.152 lb
MBJYG25-300-8 563622 150 A 0.059" 49.34 kcmil 11.811" 0.335" 0.866" 1.102" 0.181 lb

nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

IEC is a registered trademark of the International Electrotechnical Commission.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Brochures

Wind Power Solutions
1.94 MB English

Certifications

cUL KDER7.E220029
CSA C22.2 No. 41
UL KDER.E220029
ANSI/UL 467

Instruction Sheets