Features

  • Cost effective surge solution for telecom base stations, protecting circuits at the point of entry
  • Environmentally robust enclosure for use in harsh conditions

Specifications

Part Number TSP48V12W
Nominal System Voltage (Un) 0 - 48 VDC
Max Continuous Operating Voltage (Uc) 65 VAC
65 VDC
Nominal Discharge Current (In) 20 kA 8/20 μs
Max Discharge Current (Imax) 40 kA 8/20 μs
Voltage Protection Level (Up), + to - 280 V @ 3 kA
Voltage Protection Level (Up), + to - @ In 600 V
Short Circuit Current Rating (SCCR) 25 kA
Frequency 0 – 60 Hz
Protection Modes Common
Differential
Remote Contacts Yes
Status Indication Mechanical flag
Remote Contacts
Technology MOV with thermal disconnect
Connection, Stranded #4 Max
Temperature -40 to 176 °F
Enclosure Material Acrylonitrile Butadiene Styrene
Polycarbonate
Enclosure Rating IP 66
Mounting Wall mount
Depth (D) 8.27"
Height (H) 20.47"
Width (W) 15 3/4"
Unit Weight 23 lb

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.