United StatesChange
nVent CADDY

Multi Attachment

Features

  • Disperses load over two anchors
  • Minimizes the number of installed braces needed for concrete and wood structures
  • Ideal for deck installations
  • Use for both lateral and longitudinal sway brace applications
  • Meets NFPA®-13 requirements for seismic sway bracing

Specifications

Material: Steel
Finish: Electrogalvanized
Part Number Hole Size 1HS1 Hole Size 2HS2 A B C D UL Listed Load
CSBMA050050EG 9/16" 9/16" 12" 2 1/2" 2 1/2" 9" 3,740 lb
CSBMA050075EG 13/16" 9/16" 12" 2 1/2" 2 1/2" 9" 3,740 lb
UL Loads
Part Number Service Pipe Size Rating
CSBMA050050EG 1" - 12" 3,740 lb
CSBMA050075EG 1" - 12" 3,740 lb
FM Loads
Part Number Horizontal Capacity per Installation Angle from Vertical
30° - 44° 45° - 59° 60° - 74° 75° - 90°
CSBMA050050EG 3,290 lb 4,520 lb 5,540 lb 6,200 lb
CSBMA050075EG 3,290 lb 4,520 lb 5,540 lb 6,200 lb
Mount to structure using holes indicated in HS1.

nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

FM is a registered certification mark of FM Approvals LLC, LTD.
NFPA is a registered trademark of National Fire Protection Association, Inc.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Applications

Video