Rail Secondary Power Surge Protector, DC Circuits

Features

  • Hybrid TVSS technology
  • High surge rating provides a high level of protection and long operational life
  • Low let-through voltage
  • Sine wave filter for RFI/EMI attenuation

Specifications

Part Number EPD1224ATAAR1
Nominal System Voltage (Un) 12 VDC
24 VDC
Max Continuous Operating Voltage (Uc), 12 VDC 18 VDC
Max Continuous Operating Voltage (Uc), 24 VDC 36 VDC
Voltage Protection Level, 12 VDC (Up) 34 V @ 20 kA
Voltage Protection Level, 24 VDC (Up) 41 V @ 20 kA
Rated Load Current (IL) 30 A
60 A
Filtering -65 dB @ 100 kHz
Distribution System Two wire
Aggregate Surge Rating 20 kA 8/20 μs
Status Indication LED
Technology Metal Oxide Varistor (MOV)
Silicon Avalanche Diode (SAD)
In-line series filter
Connection Type AAR Terminals
Protection Modes -ve to +ve
Humidity 0 – 90 % RH
Temperature -40 to 158 °F
Enclosure Material UL® 94V-0 thermoplastic
Enclosure Rating IP 20
NEMA®-1
Depth (D) 4.73"
Height (H) 2.37"
Width (W) 4.73"
Unit Weight 1.92 lb
Complies With ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ANSI is a registered trademark of American National Standards Institute.
IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
NEMA is a registered service mark of National Electrical Manufacturers Association.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Applications

Video

Brochures

Technical

Warranties