United StatesChange
CADDY

103 Loop Hanger with Insulation Shield

1030600EG

  • Details
  • Applications
  • Video
  • Documents
  • 3D Models

Features

  • Recommended for the suspension of stationary insulated piping
  • Protection shield is welded to loop before plating

Specifications

Part Number 1030600EG
Material Steel
Finish Pregalvanized
Electrogalvanized
Shield Size 6"
Outer Diameter (OD) 6.62"
Rod Size (RS) 3/4"
Length (L) 6"
A 10 5/8"
B 5 3/16"
C 2 3/8"
Static Load (F) 1,250 lb
Standard Packaging Quantity 10 pc
UPC 78285636119
Insulation Shield Sizing Chart for Iron Pipe
Nominal Iron Pipe Size Insulation Thickness
1/2" 3/4" 1" 1 1/2" 2" 2 1/2"
1/2" 2" 2" 2 1/2" 3 1/2" 5" 6"
3/4" 2" 2 1/2" 2 1/2" 3 1/2" 5" 6"
1" 2" 2 1/2" 3" 4" 5" 6"
1 1/4" 2 1/2" 3" 3" 5" 5" 6"
1 1/2" 2 1/2" 3" 3 1/2" 5" 6" -
2" 3" 3 1/2" 4" 5" 6" -
2 1/2" 3 1/2" 4" 5" 6" - -
3" 4" 5" 5" - - -
3 1/2" 5" 5" 6" - - -
4" 5" 6" 6" - - -
5" 6" - - - - -
Insulation Shield Sizing Chart for Copper Tubing
Nominal Copper Tube Size Insulation Thickness
1/2" 3/4" 1" 1 1/2"
1/2" 1 1/2" 1 1/2" 2 1/2" 3 1/2"
3/4" 2" 2" 2 1/2" 3 1/2"
7/8" 2" 2 1/2" 3" 3 1/2"
1" 2" 2 1/2" 3" 3 1/2"
1 1/4" 2" 2 1/2" 3" 4"
1 1/2" 2 1/2" 3" 3 1/2" 5"
2" 3" 3 1/2" 4" 5"
2 1/2" 3 1/2" 4" 4" 5"
3" 4" 5" 5" 6"
3 1/2" 5" 5" 6" 6"
4" 5" 5" - -
5" 6" 6" - -
Flared edges on sizes through 4” only.
For sizes larger than 6” see Model 403 Clevis Hanger.

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.