Features

  • No loose parts
  • No assembly required
  • Snap-off bolt head helps enable easy installation and inspection of seismic sway braces
  • Meets NFPA®-13 requirements for seismic sway bracing

Specifications

Part Number CSBIB125180EG
Material Steel
Finish Electrogalvanized
Flange Thickness (FT) 3/4" – 1 1/4"
Rod Size (RS) 1/2"
A 4" – 18"
Height (H) 3 1/2"
Length (L) 21 1/2"
Width (W) 3 1/8"
Certifications cULus
FM
OSHPD
Standard Packaging Quantity 5 pc
UPC 78285663502
EAN-13 8711893057683
UL Loads
Brace Direction to Structure Service Pipe Size Rating
Parallel 1" - 12" 3,740 lb
Perpendicular 1" - 12" 3,740 lb
FM Loads
Brace Direction to Structure Service Pipe Size Horizontal Capacity per Installation Angle from Vertical
30°- 44° 45°- 59° 60°- 74° 75°- 90°
Parallel N/A 1,620 lb 1,710 lb 1,010 lb 1,110 lb
Perpendicular N/A 1,620 lb 2,300 lb 2,820 lb 3,140 lb