United StatesChange
nVent CADDY

Adjustable I-Beam Adapter

CSBS4

Features

  • Meets requirements of the Buy American Act
  • No loose parts
  • No assembly required
  • Snap-off bolt head helps enable easy installation and inspection of seismic sway braces
  • Meets NFPA®-13 requirements for seismic sway bracing

Specifications

Part Number CSBS4
Material Steel
Finish Electrogalvanized
Flange Thickness (FT) 1/4" – 3/4"
A 4" – 14 1/2"
Rod Size 1 (RS1) 3/8"
Rod Size 2 (RS2) 1/2"
Height (H) 2 5/8"
Width (W) 3 5/8"
Certifications cULus
FM
FM Tested
OSHPD
Standard Packaging Quantity 10 pc
UPC 78285692012
EAN-13 0782856920120
UL Loads
Part Number Flange Thickness Perpendicular to Structure Parallel to Structure
CSBS3 1/4" - 3/8" 3,000 lb 2,200 lb
3/8" - 3/4" 3,000 lb 2,765 lb
CSBS4 1/4" - 3/8" 3,000 lb 2,200 lb
3/8" - 3/4" 3,000 lb 2,765 lb
CSBS5 3/4" - 1 1/4" 3,000 lb 2,500 lb
FM Loads
Part Number Horizontal Capacity per Installation Angle from Vertical
Perpendicular to Structure Parallel to Structure
30°- 44° 45°- 59° 60°- 74° 75°- 90° 30°- 44° 45°- 59° 60°- 74° 75°- 90°
CSBS3xx 1,180 lb 2,210 lb 2,830 lb 2,940 lb 820 lb 1,380 lb 2,080 lb 3,010 lb
CSBS4xx 1,180 lb 2,210 lb 2,830 lb 2,940 lb 820 lb 1,380 lb 2,080 lb 3,010 lb
CSBS5xx 1,220 lb 2,140 lb 2,580 lb 2,870 lb 1,100 lb 1,820 lb 2,190 lb 2,680 lb

nVent, nVent CADDY, nVent ERICO, nVent ERIFLEX, and nVent LENTON are owned by nVent or its global affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.

FM is a registered certification mark of FM Approvals LLC, LTD.
NFPA is a registered trademark of National Fire Protection Association, Inc.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Applications

Certifications

cUL VGMY7.EX3956
ULC/ORD-C203A
FM
1.19 MB English
FM Tested CSB/CSBS/CSBU
ANSI/FM 1950, 163 KB English
OSHPD OPM-0062-13
3.85 MB English