Surge Diverter, 10 kA Single Mode

DSD1101S440

Features

  • 10kA 8/20μs maximum surge rating provides protection suitable for small sub-distribution panels or point-of-use applications
  • Indication flag provides clear visual indication of life status

Specifications

Part Number DSD1101S440
Nominal System Voltage (Un) 380 V
Max Continuous Operating Voltage (Uc) 385 VAC
500 VDC
Nominal Discharge Current (In) 5 kA 8/20 μs
Max Discharge Current (Imax) 10 kA 8/20 μs
Voltage Protection Level (Up) 2,000 V @ 5 kA
Distribution System TN-C
TN-C-S
TN-S
Frequency 0 – 60 Hz
Protection Modes Single
Short Circuit Current Rating (SCCR) 10 kA
Technology MOV with thermal disconnect
Connection, Solid #2 Max
Connection, Stranded #4 Max
Mounting 35 mm top hat DIN rail
Enclosure Material UL® 94V-0 Thermoplastic
Enclosure Rating IP 20
NEMA®-1
Remote Contacts No
Status Indication Mechanical flag
Terminal Torque 31 in lb Max
Temperature -40 to 176 °F
Module Width 1 M
Depth (D) 3"
Height (H) 3.54"
Width (W) 0.71"
Unit Weight 0.3 lb
Complies With IEC® 61643-1 Class III
ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B
Certifications CE
Standard Packaging Quantity 1 pc
UPC 78285647026
EAN-13 8711893013962

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ANSI is a registered trademark of American National Standards Institute.
IEC is a registered trademark of the International Electrotechnical Commission.
IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.
NEMA is a registered service mark of National Electrical Manufacturers Association.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.