United StatesChange
ERICO

Replacement Module for DSD, 40 kA

DSD140M440

Specifications

Part Number DSD140M440
Nominal System Voltage (Un) 380 V
Max Continuous Operating Voltage (Uc) 440 VAC
580 VDC
Nominal Discharge Current (In), Per Mode 20 kA 8/20 μs
Max Discharge Current (Imax), Per Mode 40 kA 8/20 μs
Voltage Protection Level (Up) 1,400 V @ 3 kA
2,200 V @ 20 kA
Frequency 0 – 60 Hz
Short Circuit Current Rating (SCCR) 25 kA
Technology MOV with thermal disconnect
Enclosure Material UL® 94V-0 Thermoplastic
Status Indication Mechanical flag
Temperature -40 to 176 °F
Module Width 1 M
Depth (D) 1.91"
Height (H) 1.78"
Width (W) 0.71"
Unit Weight 0.1 lb
Certifications CE
Standard Packaging Quantity 1 pc
UPC 78285658204
EAN-13 8711893041569