United StatesChange
ERIFLEX

ERIFLEX FLEXIBAR, Tinned Copper

FLEX3MTC6X100X1 (505547)

Features

  • Thin layers of tinned electrolytic copper formed into a stack
  • Insulated by high-resistance, self-extinguishing PVC with less than 20% contact with conductor for high flexibility
  • Easily bent, folded, and twisted, improving assembly flexibility, shortening connections, and decreasing footprint
  • Dramatically smaller and more flexible than comparable cable based on ampacity
  • Better power density than cable with lower skin effect ratio
  • Connections made by punching and bolting directly through the copper laminates, clamping onto the end of the ERIFLEX FLEXIBAR, or welding using ERICO CADWELD
  • No lugs needed, reducing installation time and improving resistance to vibration
  • Weight savings and material savings compared to wire alternatives
  • Reduces total installation cost
  • Traceability codes and designation part numbers printed on insulation
  • 100% production dielectric tested
  • UL 758 Appliance Wiring Material requirements for Cold Bend testing at -40°C and -50°C (-40°F and -58°F)
  • EAC compliant
  • RoHS compliant

Specifications

Part Number FLEX3MTC6X100X1
Article Number 505547
Typical Application Current Rating 1,600 A
Finish Tinned
Material Copper
Polyvinylchloride
Dielectric Strength 20 kV/mm
Flammability Rating UL® 94V-0
Insulation Elongation 370 %
Insulation Thickness 0.08"
Nominal Voltage, UL/IEC 1,000 VAC
1,500 VDC
Operating Temperature -58 to 221 °F
Forming Temperature 32 – 131 °F
Certification Details UL® 67
UL® 758
Complies With IEC® 60439.1
IEC® 61439.1
IEC® 61439.1 Class II
Length (L) 9.84'
∆T 30 K 1,414 A
∆T 45 K 1,765 A
∆T 60 K 2,062 A
Conducting Layers (N) 6
A 3.937"
B 0.039"
Cross Section 1,184.12 kcmil
2 Bar Current Coefficient 1.6
3 Bar Current Coefficient 2.02
Certifications ABS 08-HS365878-2-PDA
Bureau Veritas 02859 BV
CE
CSA 90005
cURus
EAC 0234251 (Russian Federation)
IEC 61439-1 Class II FLEXIBAR
IEC 61439-1 FLEXIBAR
RoHS
Standard Packaging Quantity 1 pc
UPC 78285644774
ADMISSIBLE CURRENTS: This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
∆T = Temperature of conductors – Internal temperature of panel.
Refer to technical documentation for additional ampacity ratings.

Pentair, CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice.

ABS is a registered certification mark of American Bureau of Shipping.
CSA, CSA-US and C-CSA-US are registered trademarks of Canadian Standards Association.
IEC is a registered trademark of the International Electrotechnical Commission.
UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.

Applications

Video

Brochures

Catalogs

Flexible Conductors
63.23 MB English

Certifications

Bureau Veritas 02859 BV
ACE 14/163/02, 262 KB English
CSA 90005
CSA C22.2 No. 0, CSA C22.2 No. 210
cUR QEUY8.E125470
CSA C22.2 No. 29, CSA C22.2 No. 244
IEC 61439-1 Class II FLEXIBAR
IEC 61439-1 (2011), EN 61439-1 (2012), 50 KB English
IEC 61439-1 FLEXIBAR
IEC 61439-1 (2012), 50 KB English
UR AVLV2.E316390
ANSI/UL 758
UR QEUY2.E125470
ANSI/UL 67, ANSI/UL 891

Datasheets